ISS-S intumescent Steel Coating
ISS-S Paint is an intumescent paint system providing fire resistance to structural steel and cast iron of up to 120 mins with a minimum number of coats. A compatible decorative overcoat system ensures the system will enhance the building’s architectural and design features. Recomended for external exposed steel not subject to pooling water.
How it works
The heat of a fire triggers a catalytic reaction, causing the expansion of an insulating char layer up to 50 times the paint thickness. This layer keeps the steel below its critical temperature, thus maintaining the structural integrity of the building.
Fire testing
Product performance assessment is based upon UKAS/EGOLF Fire Test Laboratory Certification to BS 476 Part 21 - Fire Resistance to load bearing elements of structures. For certification and compliance with regulations the manufacturer will supply a Certificate of Supply on request.
Preparation and Pretreatment
Steel and cast iron should be free from rust and millscale and primed with HBP Primer, to 75 microns DFT (or alternative good quality anti-corrosive primer compatible with intumescent paints) in accordance with manufacturers instructions. Treat galvanised surfaces with “T” wash/Mordant solution & prime with zinc phosphate or other primer for steel. HBP Primer, may be left without further overcoating or decorated with appropriate conventional paint where no fire resistance is required.
To Specify
We are happy to provided specifications and quotations - please use our structural steel specification form to ensure we cover all aspects of your fire protection and decorative requirements in our quote. We accept any order size.
Prior to application the contractor should contact the Technical Department (see below) to obtain a basecoat application schedule.
For help please speak to the technical team on: Tel: 01329 841 416 or Email: sales@stormflame.com
Application
Recoating
Brush/roller application
Spray application
Spray Equipment
Airless Spray Pump
Use equipment recommended by manufacturer for the application of high viscosity intumescent paints.
Tip Size
Care should be taken to clean filters regularly. Cleaning should be undertaken with xylene / cellulose thinners.
Colours, Finishes & Sizes
A range of hard, high quality, weather resistant decorative finishes matches the decor, architectural or historic features of a building while helping to make it a safer structure.
Sizes: (ISS-S intumescent Steel Coating) 20kg, 5kg, 2.5kg
Colours: (FR Paint) BS4800 or RAL colours
Topcoat: FR Paint Eggshell available in 5kg and 2.5kg
Composition
Intumescent compounds and resin binders, with high opacity pigments.
VoC
The EU VoC limit for structural steel intumescent paints is 500 gm / litre. This product contains 398 gm / litre.
Technical Advisory And Estimating Service
Our in-house estimators provide realistic, confidential guidance on project costings to contractors and quantity surveyors. They also provided expert advice and assistance with all aspects of specification and application.
Application Conditions
Installation
We have technical representatives who provide assistance in the selection and specification of the products on this site and should be consulted for exact installation and product suitability. Ensure an early engagement with ourselves, designers, main contractor and specialist installers before any installation. Other trades and/or manufacturers may need to be consulted. For in-depth information, specification and technical advice please call our Head Office on Tel: 01329 841 416 or Email: sales@stormflame.com
Maintenance
All interested parties, designer, specifier, main contractor and specialist installers should provide access to allow the fire stopping seals to be regularly inspected and maintained, as well as records kept of such maintenance at minimum periods of 12 months, as required by the Regulatory Reform Order, and repaired if necessary. Reference should be made to ASFP TGD 17 – Code of Practice for the Installation and Inspection of Fire Stopping.
Competency
It is vital that those entrusted to design or install a fire stopping product have the necessary levels of competence to undertake the task professionally and thoroughly. The level of competency required will be commensurate with the expected complexity of the building. All designers must eliminate, reduce or control foreseeable risks that may arise during installation, construction or maintenance when preparing or modifying designs. Clients should ensure that the principal designer and principal contractor carry out their duties under CDM regulations. The ASFP foundation course in passive fire protection provides essential knowledge as part of demonstrating competency and understanding in this key fire protection specialism.
Additional Notes
This product can only be supplied once the Steel Paint enquiry form has been completed and approved by the manufacturer: Click the following link to go to the Steel Paint Form: Steel & Cast Iron Order Form.
Health and Safety
ISS-S Paint is a compliant specialist coating. The range of topcoats are either water-based or 2010 compliant and safe to use in accordance with manufacturer’s instructions. The EU & UK VoC limit for this product is 500 gm / litre. Product contains 398 gm / litre.
The product does not present any known health hazards during or after installation. Normal good industrial and personal hygiene practices should be observed. For further information on health and safety please see the Safety Data Sheets (SDS) or please contact the technical team on Tel: 01329 841 416 or Email: sales@stormflame.com
More information / Data sheet
For more information please click the button below to download a printable PDF file for ISS-S intumescent Steel Coating.
SHOP >>
Stormflame offer a comprehensive range of fire and non fire rated construction products for use in walls, floors, ceilings, doors, ducts and other compartmentation structures.
The above information to the best of our knowledge is true and accurate and based upon current test data and is supplied for your guidance only. Customers should satisfy themselves to the suitability of the product in its intended use and no guarantee is given or implied since the conditions of actual use are beyond our control. We disclaim any liability for loss, damage or other expense arising from the use of information, data or products mentioned or referred to and reserve the right to change any details or specifications without notice.
Copyright © intumescent-Paint 2021. Unit 9, The I.O Centre, Stephensons Road, Segensworth, Fareham, PO15 5RU
tel: 01329 841 416 | fax: 01329 841 417 | email: sales@stormflame.com